2.3 WIRING DESCRIPTION
The wiring method for the MCP SERIES is shown in Figure A.
Figure A - Wiring Diagram for MCP 6001, & MCP10001
REAR VIEW
Wiring Instructions:
1. Utility panel circuit breaker required is 35A or larger
2. Utility wire guage must be 8 guage or larger.
3. Connect utility per drawing.
4. Connect output load connections and jumper wires for correct voltages per drawings.
5. Use proper size AWG wires for all connections.
6KVA
ONLY
10KVA
ONLY
NOTE: PARA SYSTEMS DOES NOT PROVIDE AC OUTPUT OVERCURRENT PROTEC-
TION. OUTPUT OVERCURRENT PROTECTION IS TO BE PROVIDED BY THE USER.